roofkey Roofing Guidelines
The roofkey Roofing Guidelines are here to help
both the
Property Owner and
Roofing Contractor
have a good quality roof installation
that passes the roof inspection
and greatly reduces the chance of roof leaks,
other roofing problems, callbacks
and litigations.
Building Codes and Manufacturer’s specifications can sometimes be
conflicting and can vary from one area to another. See
Building Code Conflicts web page.
Each of the roofkey Roofing Guidelines listed below is recognized by one or
more City/County Building Departments, however, which roofing guidelines they
each recognize varies. Most recognize at least 80 percent or more and a few almost
100 percent.
Just because your roof is located in one area does not mean it should be
roofed to a lower standard, thereby increasing the chance of developing roof
leaks, or other roofing problems, callbacks and possible litigation.
Many Roofing Contractors will bid the roof to the local building code only,
just to get the job. They fail to let the property owner know of the many
other choices there are to greatly reduce the chance of problems occurring.
The roofkey Roofing Guidelines below provide property owners with information so
they can make the decisions, not the Roofing Contractor, on how they want their
roof installed.
The roofkey Roofing Guidelines listed below address only some of the roofing
materials and/or circumstances that occur with roofing installations.
Failure to follow these roofkey Roofing Guidelines will result in a correction
being written in our Roof Inspection Service Report we give to our customers.
The roofkey Roofing Guidelines below are based upon weather conditions that
effect and dictate the use of roofing materials and their installation.
This is called Building Design Criteria.
roofkey Minimum Design Criteria for Roofing
Local City/County Building Design Criteria for roofing will be used if more
stringent than what is listed below. Example might be as you move west and
up in elevation the wind speed and the ground snow load criteria increases.
-
100 mph 3-second gust wind speed or 85 mph fastest mile wind speed
-
30 pounds per square foot ground/roof snow load
-
Wind Driven Snow Area
-
Ice Damming at eaves
-
3.0 inches per hour for 100-Year, 1-Hour Rainfall (for roof drain sizing)
-
Moderate or Severe Hail Exposure Area
Property Owners may opt out of some of the roofkey Roofing Guidelines listed
below at their own risk if they are not required by their Local Building
Department. However, if you, the Property Owner, incur damage as a result
of your choice to opt out of any of the roofkey Roofing Guidelines,
remember it is at your own risk, not the Roofing Contractor's responsibility to
fix it.
We highly recommend that you, the Property Owner, do not opt out of any of
the roofkey Roofing Guidelines even if one or more are not recognized or
enforced by your Local Building Department. Building Departments make
mistakes too causing litigation between Property Owners or litigation between
the Roofing Contractor and the Property Owner.
RE/COR Inc. and its employees will write a Correction on our Roof Inspection
Report if any of the roofkey Roofing Guidelines are not followed whether your
Local Building Department requires or enforces the roofing guidelines listed
below or not.
roofkey Roofing Guidelines
General Guidelines for all Sloped Roof Coverings
- Existing Roof Coverings: Removal of All is required.
- Deteriorated Decking: The decking must be removed where the decking is
water soaked or deteriorated. Additional decking will be required if the
existing decking will not provide a sound, level, and rigid surface.
Example: Old 3/8” decking will need to be overlaid with new code approved
decking material.
- Underlayment: All underlayments are required to be labeled with the
appropriate ASTM numbers.
- Ice and Water Membrane: An underlayment of an
ASTM D 1970 ice and water membrane (self adhering polymer modified bitumen
sheet) or
equal is required at ALL eaves of sloped roofs applied directly to the
decking and up the roof slope two (2) feet past the exterior wall line. In
the case of a patio cover that has a minimum of three (3) open sides, an ice
and water membrane is only necessary three (3) feet up the roof from the
eave. Exception: Detached accessory structures that contain no conditioned
floor area do not require an ice and water membrane.
- Metal Drip Edge: A metal drip edge is required at the eaves of all
roofs.
- Fastener Heads: Fasteners shall be flush with the roofing material’s
surface, NOT over driven, under driven, or crooked for all roofing
materials.
- Fasteners: IRC/IBC approved Corrosion Resistant
Fasteners are required with the installation of all roofing materials and
accessories including battens.
- Weather Exposure: Maximum weather exposure shall not be exceeded.
Check manufacturer’s specifications before installation. When a staggered
installation is performed, the coursing of all roofing materials must be
dropped so that the distance between the butt of the lowest roofing material
in one course and the highest butt in the course above does not exceed the
maximum weather exposure allowed.
- Flashing: All rusted, damaged, or
deteriorated roof flashing, vent flashing, metal edging, drain outlets,
collars, and metal counter flashing must be replaced.
- Exterior Cladding: Siding, Stucco, Brick or Stone veneer and any other
type of cladding must be kept up off the roof surface a minimum of 1 1/2"
for Steep-Sloped Roofing and 6" for Flat Roofing at all rake walls, head
walls, parapet walls and chimneys. Cladding of any type can not be setting
down on the surface of the roofing material. Check with the manufacturer of
the cladding because some such as James Hardie
www.jameshardie.com require their
fiber cement siding to be a minimum of 2" above the surface of the roof in
areas with elevations above 4000 feet.
- Vertical Blocking and "Z" Bar flashing: A Vertical Blocking piece of
lumber and "Z" Bar Flashing equal to the thickness of the cladding is to be
used at all rake walls, head walls, parapet walls, and chimneys for the
termination edge of all exterior cladding. The roof flashing shall be
placed on the outside of the vertical blocking material and under the "Z"
bar flashing. This Roofing Guideline is most needed if the cladding is made
of stone or brick veneer even stucco or other materials where the roof
flashing cannot be easily removed in the future without damaging the
cladding. This Roofing Guideline also applies to lap siding or any other
type of exterior cladding.
- Roof Ventilation: Proper ventilation per IBC and IRC is required for
all roof installations for both new roof construction and when replacing an
existing roof covering. Check structure for Cathedral Ceilings.
Check for a minimum of 1" gap for air flow between the top of the insulation
and the underside of the roof decking. Soffit or Eave Vents may need to
be added in addition to Ridge Vents.
- Material Defects: The Roofing Contractor is responsible for culling out
all off grade and detectable defects in all roofing materials and
accessories.
Roofing Guidelines for Asphalt Shingles
- Layers of Roofing: The maximum number of layers of roofing is one (1)
with Asphalt Shingles in Moderate or Severe Hail Prone Areas such as
Colorado. When one (1) or more layers of roofing exist, all layers of
roofing must be removed prior to the installation of a new roof.
- Existing Decking: New decking overlay is
required for asphalt shingles if old existing decking is made of lumber
which is larger than 1” x 6” pieces of lumber or if the gaps between the
boards are more than 1/8”.
- Minimum Slope: The minimum slope is 4:12 for standard
single ply underlayment installation. For slopes above 2:12 and less than
4:12 an underlayment of two (2) plies (lapped 19") of ASTM D 226 or D
4869 Type I or II underlayment (commonly referred to as15# or 30# base felt) or equal is required.
Other approved equal underlayments that are ASTM numbered may be used as
long as they are also applied in the same two ply fashion.
- Metal Drip Edge: A metal drip edge is required at both rake edges and
eaves with Asphalt Shingles.
- Number of Fasteners: A Minimum of six (6) fasteners are required for all
strip type shingles. (Some shingles require 8 nails for higher wind areas.
See manufacturer’s specifications.)
- Location of Fasteners: Corrosion resistant fasteners shall be located
per manufacturer’s instructions and not placed in factory applied adhesive.
Nails must also penetrate both parts of a laminated shingle. Check
manufacturer’s specifications and association manuals for the correct
placement of nails across the length of the shingle.
- Over Driven Fasteners: Fasteners that have been over driven require
the sealing of the over driven fastener head and adding a new properly
placed and driven fastener.
- Mansard Roof Shingle Fastening: Mansard roof
applications also require the butts of all asphalt shingles to be hand
sealed down in addition to six nails for each shingle per the Asphalt Manufacturer's Association Manual.
Call for a roof inspection before shingles are fully and completely sealed
down.
This makes it easier to properly inspect the fasteners.
Roofing Guidelines for Cedar Shakes and Shingles
- Solid Decking: Is required for Cedar Shakes in Wind Driven Snow Areas.
- Minimum Slope: Minimum slope is 4:12 for cedar shakes and 3:12 for
cedar shingles with reduced coursing. For shake roof coverings over
non-living areas with slopes above 3:12 and less than 4:12, an underlayment
of an ice and water membrane is acceptable by many in the roofing industry
including us and some Building Departments for re-roofing only, but not new
construction.
- Underlayment/Interlayment: In addition to the
required single ply ASTM D 226 Type II underlayment (commonly referred to as
30# base felt) or equal, an 18" ASTM D 226 Type II interlayment
(commonly referred to as 18" 30# lace felt) is required to be laced in
between each course of shakes.
- Metal Drip Edge: A metal drip edge is required at both rake edges and
eaves with Cedar Shakes and Shingles.
- Shake Placement: Correct placement of the shakes or shingles is
critical. The maximum gap between the sides for each shake is 5/8”. The
maximum gap between the sides for each shingle is 3/8”. The sides of each
shake or shingles should never touch. The minimum side lap is 1 ½” between
joints in adjacent courses for all cedar shakes and shingles.
- Location of Fasteners: Corrosion resistant nails shall be
placed to the manufacturer’s specifications and industry standards, not too
high or too low or too far from the sides of the cedar shake or shingle.
See Cedar Shake & Shingle Bureau’s
www.cedarbureau.org specifications.
Roofing Guidelines for Clay and Concrete Tile
- Minimum Slope: Minimum slope is 3:12 for standard installation of most
concrete and clay tile. For slopes 2 ½:12 to 3:12 an approved flat roofing
membrane is required. The tile and battens are then attached without
fasteners penetrating the flat roofing membrane. However, the minimum slope
is only 5:12 for some clay tile. Always, check with the manufacturer for
low-slope application specifications.
- Underlayment: An underlayment of two (2) plies
(lapped 19") of
ASTM D 226 Type II underlayment (commonly referred to as 30# base felt)is
required. Other approved equal underlayments that are ASTM numbered may be
used as long as they are also applied in the same two ply fashion. A single
ply of ASTM D 6380 or D 3909 Class M mineral surfaced rolled roofing
(commonly referred to as 90 pound granulated rolled roofing) may also be used as an
alternative underlayment.
- Vertical Battens: Vertical battens or risers of a minimum 3/8"
thickness and made of cedar or decay resistant treated wood or other decay
resistant materials are required under the horizontal battens and over the
underlayment. (vertical battens are sometimes referred to as
wood lath which is generally 1 1/2" wide and 4' long) The spacing
depends on the size of the horizontal battens based on the total roof loads
for deflection. (See manufacturer’s specifications.)
- Horizontal Battens: When using nominal dimensional lumber for
horizontal battens such as 1 x 2s, 1 x 4s, 1 x 6s, etc. the minimum
dimensions are ¾” x 1 ½", ¾” x 3 ½”, ¾” x 5 ½” respectively. It is ok to
use lumber that is slightly shy of the minimum dimensions as long as the
distance between the vertical battens is narrowed appropriately.
- Batten Fasteners: Corrosion resistant staples with 7/16" crown may be
used to fasten down the horizontal battens if the vertical battens or risers
are on a maximum of 12" centers. Greater spacing of the vertical battens or risers
requires 8d common corrosion resistant nails.
- Field Tile Fasteners: Corrosion resistant nails or screws with minimum
5/16" heads are required for fastening of filed tile.
Approved fasteners
shall penetrate through the horizontal battens but not penetrate the
underlayment. Approved corrosion resistant #8 screws may be used as an
alternate.
- Field Tile Fastening: Each and every Field Tile is required to be
fastened down with one fastener if installing lugged tile and two fasteners
if installing a non-lugged tile.
- Hurricane Clips: Hurricane clips are required for each tile at all
eaves placed near their butts.
- Primary Flashing: A primary flashing to keep water on the surface of
the field tile as much as possible is required at all Plumbing, Heat, and
Mechanical Vents.
- Weather Blocking Material / Primary Flashing: From the Tile
Manufacturer's Manual, both the 1997 for Cold Climate and the 2006 for
Moderate Climate, “Openings at the Hips, Ridges, and Headwalls including
Chimneys, Skylights, Solar Panels, and Down Slope Horizontal Abutments shall
be fitted with weather blocking material to keep water on the surface of the
field tile.” This means a Weather Blocking Material such as a Primary
Flashing to keep water on the surface of the field tile as much as possible
is also required at all Rake Walls, Headwalls, Chimneys, Skylights, Swamp
Coolers, Curbs, and any Other Protrusion through the tile roof or object
setting on the roof, not just the Hip & Ridge. This flashing must be fully
down on the surface of the field tile so that wind driven snow or rain cannot get up under it.
- Secondary Flashing: A secondary flashing is required to be roofed
into/over the underlayment at all Jacks, Vents, Head Walls, Rake Walls,
Chimneys, Skylights, Swamp Coolers, Curbs, and any Other Protrusion through
the tile roof or object setting on the roof.
Roofing Guidelines for Flat Roofing Membranes
- Layers of Roofing: The removal of All existing Roof Coverings is
required where there exists (2) two or more layers of any type of Roof
Coverings. (1) One overlay over (1) one existing layer of an approved flat
roofing membrane is permitted provided the existing Roof Covering's surface
has been properly prepared to the manufacturer's specifications.
- Minimum Slope: New construction shall have a minimum ¼” slope and
Positive Roof Drainage (no standing water after 48 hours). Re-roofing of an
existing structure must also have Positive Roof Drainage (no standing water
after 48 hours). Sometimes extra drains/scuppers and/or crickets will
need to be added.
- Drains / Scuppers: Secondary or overflow drains/scuppers are required
2" above the primary drains on all roofs having walls/parapet walls and shall discharge above grade and be
independent of primary drains/scuppers.
- Ballasted Roofs: Ballasted roofing membranes must follow the criteria
set forth in the IBC and ANSI / SPRI RP-4 for the amount of ballast used in
the field, at perimeters, and at corners, etc. depending on the height of the
building and its parapet walls and if building is in an A, B, C Exposure.
Depending on Exposure and Height of structure, a ballasted roof system may
be prohibited. (See Section 1504.8 of the 2006 IBC.)
End of roofkey Roofing Guidelines.
The roofkey Roofing Guidelines above may change in the future as Building
Codes, Evaluation Service Reports, Manufacturer Specifications or Manuals
evolve. Also, the above roofkey Roofing Guidelines may change if there is
some other new roofing material and/or circumstance that occurs with roofing
installations that we become aware of or an existing one rises to the degree of
being a major problem.